Locations Requiring Consideration of Fire Resistant Measures [Pg.172]

Vessel, tank and piping supports in fire hazardous zones. [Pg.172]

Onshore 2 inches of Concrete UL 1709, 2 hour rating Offshore Ablative or intumensent materials, UL 1709, 2 hour rating Cable Trays Stainless steel cabinets or fire rated mats, UL 1709, 20 minute rating ESD Control Panels. Stainless steel cabinets or fire rated mats, UL 1709, 20 min. rating EIVs. (If directly exposed) -Stainless steel cabinets or fire rated mats UL 1709, 60 min. EIV actuators Stainless steel cabinets or fire rated mats UL 1709, 20 minute rating Firewalls  [Pg.172]

Onshore Concrete or masonry construction, UL 1709, 2 hour rating Offshore Ablative, composite or intumensent, UL 1709, 2 hour rating [Pg.172]


LOCATIONS REQUIRING CONSIDERATION OF FIRE RESISTANT MEASURES... [Pg.269]