PRDs Set Pressure and Overpressure per ASME Code

Some system uses one pressure relief device for overpressure protection, but some uses more than one. Some relief contingency is non-fire, but some is caused by fire. ASME Section VIII (ASME code) has some guideline for PRD set pressure and accumulated pressure for different cases, see Table 1. [Pg.149]

Per ASME code, Table 1 non-fire case is for equipment MAWP 30 psig. For equipment MAWP Is between 15 to 30 psig, the allowable accumulated pressure for single PRD case is 3 psi, and for multiple PRD case is 4 psi, [Pg.150]

PRD maximum set pressure per ASME code is based on MAWP, but MAWP is available only aAer the equipment is made. During design stage , many times, process engineer has to use equipment s design pressure as PRD s set pressure since MAWP is not available. Fortunately, in most cases, equipment s design pressure is very close (equal or less) to MAWP. [Pg.150]

Supplement PRD is an additional PRD used to protect system from fire or other external heat source. It is an [Pg.150]

As mentioned in Section IV, because of unavailable of MAWP during earlier design stage of project, most times, PRD set pressure is selected to be the same as equipment design pressure. [Pg.150]