Guide vane position

Inlet guide vane position or suction throttle valve position will also affect compressor performance. Figure 7c shovii the effect of inlet guide vane position on compressor performance. The efiect of pinch suction throttle valve is similar to reduce compressor s speed. It will reduce compressor s head generation. [Pg.49]

The two principal elements of evaporator control are evaporation rate a.ndproduct concentration. Evaporation rate in single- and multiple-effect evaporators is usually achieved by steam-flow control. Conventional-control instrumentation is used (see Sec. 22), with the added precaution that pressure drop across meter and control valve, which reduces temperature difference available for heat transfer, not be excessive when maximum capacity is desired. Capacity control of thermocompression evaporators depends on the type of compressor positive-displacement compressors can utilize speed control or variations in operating pressure level. Centrifugal machines normally utihze adjustable inlet-guide vanes. Steam jets may have an adjustable spindle in the high-pressure orifice or be arranged as multiple jets that can individually be cut out of the system. [Pg.1148]

The final element is the compressor guide-vane mechanism. The guide vanes are adjusted by means of a positioning cylinder. This cylinder is operated by a servo valve that receives a signal from the flow controller. [Pg.362]

Throttling of the suction of centrifugal and axial compressors wastes less power than throttling the discharge. Even less power is wasted by adjustment of built-in inlet guide vanes with a servomechanism which is a feedback control system in which the controlled variable is mechanical position. Speed control is a particularly effective control mode, applicable to large units that can utilize turbine or internal combustion drives control is by throttling of the supply of motive fluids, steam or fuel. [Pg.59]

Figure 9c Pressure control by varying inlet flow, [5] Figure 9d Volume flow control by varying inlei guide vane s position. [5]... Figure 9c Pressure control by varying inlet flow, [5] Figure 9d Volume flow control by varying inlei guide vane s position. [5]...

See other pages where Guide vane position is mentioned: [Pg.189]    [Pg.678]    [Pg.720]    [Pg.52]    [Pg.189]    [Pg.678]    [Pg.720]    [Pg.52]    [Pg.274]    [Pg.399]    [Pg.261]    [Pg.220]    [Pg.482]    [Pg.396]    [Pg.202]    [Pg.1697]    [Pg.337]    [Pg.119]    [Pg.249]    [Pg.956]    [Pg.244]    [Pg.262]    [Pg.263]    [Pg.351]    [Pg.67]    [Pg.973]    [Pg.990]    [Pg.1104]    [Pg.336]    [Pg.99]    [Pg.99]   