Disposal of effluent water from multijet ground flare seal drums should comply with paragraphs (1), (2), and (3) above, except that ... [Pg.276]

Preferably, the HjS flare system should consist of a segregated header and separate line routed up the side of a conventional elevated flare stack, sharing the same structure, pilots and igniters. However, the HjS header may be tied into the regular flare seal drum if there are special mechanical design problems associated with the separate stack e.g., in the case of a flare which is to be dismantled for overhaul. Flare elevation must be sufficient to meet atmospheric pollution and ground level concentration requirements for the sulfur dioxide produced. [Pg.279]

For services where ambient or inlet temperamres may fall below 0°C, flashback protection is provided by a special seal drum or loop seal in the inlet line. This equipment is designed specifically for the particular liquid and vapor materials being flared. In these cases a 150 mm minimum water layer is included in the bottom of the pit to prevent oil seepage into the ground, and the hydrocarbon inlet distributor is mounted 150 mm above the water surface. Details of the inlet distributor are shown in Figure 5. [Pg.267]