Example of adiabatic humidification

Develop a simple expression for the humid volume of moist air. [Pg.93]

Humid volume is defined as the volume of 1 lb of dry air plus the volume of water vapor in the air. Hence, [Pg.93]

A cooling tower operation is designed without any recycle stream. Approximately 700,000 lb/hr of hot process water at 140°F is to be cooled and returned to the process operation. Moist air is used as the cooling medium and is fed at a rate of 5.5 X 106 ft3/hr. The dry- and wet-bulb temperatures of the incoming air are 80°F and 60°F, respectively. The air leaves the tower with an estimated wet-bulb temperature of 95°F and a dry-bulb temperature of 100°F. Estimate the temperature of the water returned to the process operation. [Pg.93]


See other pages where Example of adiabatic humidification is mentioned: [Pg.92]   