V-Cone Flowmeter

Post-Oil Energy Technology After the Age of Fossil Fuels [Pg.438]

The V-cone flowmeter requires less upstream straight pipe and maintains the square root relationship between flow and pressure drop at lower Reynolds numbers than does an orifice plate. (Courtesy of McCrometer Div. of Danaher Corporation.) [Pg.438]

The basic rangeability of this meter is the same as that of an orifice plate (3 1), but if two (a high span and a low span) transmitters are used, and the flow element is accurately calibrated over the complete flow range, it can be increased to 10 1. This performance can be obtained from all properly calibrated d/p flow elements, not just from the V-cone design. The V-cone flowmeter should be installed horizontally so that the two pressure taps are at the same elevation. This guarantees that the d/p cell will detect a zero pressure differential when there is no flow. [Pg.438]


See other pages where V-Cone Flowmeter is mentioned: [Pg.436]    [Pg.436]   