Relative humidity tends to be much higher at night than during the day. Consequently, the critical period for the formation of cooling tower-induced [Pg.144]

In places in which ground fog is undesirable, the dry-wet mechanical-draft cooling tower is the best solution. It will have its wet peaking tower out of service during the cooler months of the year, thereby substantially eliminating the fog problem and totally eliminating the icing problems of wet towers. [Pg.145]