The cooling tower, which is an efficient air scrubber can easily become a catchall for contaminants resulting from the location of the tower or from the industrial process. In arid areas, ingress of sand contributes to fouling, which reduces efficiency and contributes to biofilm and under-deposit corrosion. In coastal areas, sand laden with chlorides can cause corrosion of stainless steel components and impair chemical corrosion inhibitor performance. Heavy industries, such as steel or aluminum manufacture, produce severely contaminated cooling water resulting from direct contact with metal slags and lubricants. [Pg.10]