Big Chemical Encyclopedia

Chemical substances, components, reactions, process design ...

Articles Figures Tables About

Ground fault protection schemes restricted

These are protection CTs lor special applications such as biased differential protection, restricted ground fault protection and distance protection schemes, where it is not possible to easily identify the elass of accuracy, the accuracy limit factor and the rated burden of the CTs and where a full primary fault current is required to be transformed to the secondary without saturation, to accurately monitor the level of fault and/or unbalance. The type of application tind the relay being used determine the knee point voltage. The knee point voltage and the excitation current of the CTs now form the basic design parameters for such CTs. They are classified as class PS CTs and can be identified by the following characteristics ... [Pg.479]

Figure 21.14 Scheme for a three-phase three-wire restricted ground fault protection for an FIT system... [Pg.689]

Where three CTs for unrestricted or four CTs for restricted ground fault or combined O/C and G/F protections are employed in the protective circuit, the VA burden of the relay is shared by all the CTs in parallel and a normal VA CT may generally suffice. Such is the case in most of the protective schemes discussed in Sections 21.6 and 15.6.6(1), except for those employing only one CT to detect a ground fault condition, such as for a generator protection with a solidly grounded neutral (Figure 21.12). [Pg.474]

I A restricted ground fault is recommended for equipment that is grounded, irrespective of its method of grounding. Unless the protection is restricted, the equipment may remain unprotected. Generally, it is an equipment protection scheme and is ideal for the protection of a generator, transformer and all similar... [Pg.689]

A delta-connected or an ungrounded star-connected winding should also be protected through a restricted ground fault scheme, otherwise it will remain unprotected. There is no zero sequence or residual current in such a winding to detect a ground fault. [Pg.690]

This is the most common scheme in normal use for any power system with more than one feeder, connected to a common bus, such as for distribution and sub-distribution power networks, having a number of load points, controlled through a main incoming feeder. In a switchgear assembly, for instance, common protection may be provided at the incoming for a ground fault or combined 0/C and G/F protections as discussed above. In such cases, a restricted G/F protection may not be appropriate or required, as the protection now needed is sy.stem protection, rather than individual equipment proteelion. The incomer must operate whenever a fault occurs at any point on the system. Moreover, for an LT system, where it may not be desirable or possible to provide individual protection to each feeder, such a scheme is adopted extensively. [Pg.690]


See other pages where Ground fault protection schemes restricted is mentioned: [Pg.689]    [Pg.689]   


SEARCH



Ground fault

Ground fault protection schemes

Ground protection

© 2024 chempedia.info