Even for this simplest CCGT plant, iterations on such a calculation are required, with various values of p, in order to meet the requirements set on T, the steam turbine entry temperature, and 7s (the calculated value of 7s has to be such that the dewpoint temperature of the gas (7jp) is below the economiser water entry temperature (7b) and that may not be achievable). But with the ratio /i satisfactorily determined, the work output from the lower cycle Wl can be estimated and the combined plant efficiency obtained from... [Pg.119]

The reason for using feed heating to set the entry feed water temperature at a level T, above the condenser temperature is that Tb must exceed the dewpoint temperature Tjp of the exhaust gases. If is below Tjp then condensation may occur on the outside of the economiser tubes (the temperature of the metal on the outside of the tubes is virtually the same as the internal water temperature because of the high heat transfer on the water side). With Tb > Tjp possible corrosion will be avoided. [Pg.120]

This is essentially the approach adopted by Ruffi [9] in a comprehensive set of calculations, but he assumed that the economiser entry water temperature 7b is raised above the condenser temperature by feed heating, which was specified for all his calculations. The T,s diagram is shown in Fig. 7.6 the feed pump work terms are neglected so that h.j, = hy and h. = /ib. [Pg.119]


See other pages where Temperature economiser water entry is mentioned: [Pg.122]    [Pg.123]    [Pg.128]   
See also in sourсe #XX -- [ Pg.119 , Pg.120 ]




SEARCH



Water temperatures

© 2024 chempedia.info