Table H.lc. Data for earth resistance, touch voltage, ground potential rise and corner mesh voltage for different grid and rod designs... Table H.lc. Data for earth resistance, touch voltage, ground potential rise and corner mesh voltage for different grid and rod designs...
Case A. The resistivity of the lower soil was chosen to be a moderate value of 100 ohm-m. Low values of resistance to earth at the pole, R p, were easily obtained. The main criterion is that the corner mesh voltage L must be less than the 50 kg touch voltage iitouchso- Only one case A.6 satisfies this criteria, 343 volts is less than 361 volts. This case requires a relatively large site area of 256 m for a pole and its associated equipment. [Pg.596]


See other pages where Corner mesh voltage is mentioned: [Pg.714]    [Pg.554]   